Technical specifications

Adjustment range undelayed short-circuit release3200 - 38400A
With integrated under voltage releaseNo
Type of electrical connection of main circuitOther
With switched-off indicatorNo
Number of auxiliary contacts as normally closed contact0
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitConnection at separate chassis part
Type of control elementRocker lever
Overload release current setting800 - 1600A
Device constructionBuilt-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact0
Adjustment range short-term delayed short-circuit release2 - 10A
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionNo
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP20
Rated permanent current Iu1600A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA