Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Overload release current setting320 - 800A
Adjustment range undelayed short-circuit release2 - 18A
Adjustment range short-term delayed short-circuit release2 - 10A
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionYes
Type of electrical connection of main circuitOther
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Position of connection for main current circuitConnection at separate chassis part
With switched-off indicatorNo
Motor drive optionalYes
Complete device with protection unitYes
Type of control elementRocker lever
Motor drive integratedNo
Degree of protection (IP)IP20
Rated permanent current Iu800A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user