Rated permanent current Iu160A
Rated voltage690 - 690V
Overload release current setting64 - 160A
Adjustment range undelayed short-circuit release2 - 18A
Adjustment range short-term delayed short-circuit release320 - 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Device constructionBuilt-in device fixed built-in technique
Power loss21.12W
Number of auxiliary contacts as normally open contact0
Integrated earth fault protectionNo
Type of electrical connection of main circuitScrew connection
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalYes
Number of auxiliary contacts as normally closed contact0
With switched-off indicatorNo
Number of auxiliary contacts as change-over contact0
With integrated under voltage releaseNo
Number of poles3
Position of connection for main current circuitFront side
Motor drive optionalYes
Type of control elementRocker lever
Complete device with protection unitYes
Motor drive integratedNo
Degree of protection (IP)IP20
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMN2-PX160-NA | Circuit-breaker, 3p, Ic=35kA(480V), In=160A, selective, PXR25 (lsi), fixed,

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

160A

Rated voltage

690 .. 690V

Overload release current setting

64 .. 160A

Adjustment range undelayed short-circuit release

2 .. 18A

Adjustment range short-term delayed short-circuit release

320 .. 1600A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Device construction

Built-in device fixed built-in technique

Power loss

21.12W

Number of auxiliary contacts as normally open contact

0

Integrated earth fault protection

Type of electrical connection of main circuit

Screw connection

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

With switched-off indicator

Number of auxiliary contacts as change-over contact

0

With integrated under voltage release

Number of poles

3

Position of connection for main current circuit

Front side

Motor drive optional

Type of control element

Rocker lever

Complete device with protection unit

Motor drive integrated

Degree of protection (IP)

IP20