Technical specifications

Rated permanent current Iu630A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz37kA
Adjustment range undelayed short-circuit release1260 - 15120A
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release2 - 10A
Integrated earth fault protectionNo
Number of auxiliary contacts as normally open contact0
With switched-off indicatorNo
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitScrew connection
Number of poles4
Position of connection for main current circuitFront side
Complete device with protection unitYes
With integrated under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
Type of control elementRocker lever
Rated voltage690 - 690V
Overload release current setting252 - 630A
Motor drive optionalYes
Motor drive integratedNo
Number of auxiliary contacts as change-over contact0
Degree of protection (IP)IP20
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMN4-4-PX630/VAR | Circuit-breaker, 4p, Icu=50kA(415V), In=630A, selective, PXR25 (lsi), fixed,

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

630A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

37kA

Adjustment range undelayed short-circuit release

1260 .. 15120A

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

2 .. 10A

Integrated earth fault protection

Number of auxiliary contacts as normally open contact

0

With switched-off indicator

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Screw connection

Number of poles

4

Position of connection for main current circuit

Front side

Complete device with protection unit

With integrated under voltage release

Device construction

Built-in device fixed built-in technique

Type of control element

Rocker lever

Rated voltage

690 .. 690V

Overload release current setting

252 .. 630A

Motor drive optional

Motor drive integrated

Number of auxiliary contacts as change-over contact

0

Degree of protection (IP)

IP20