Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu125A
Rated voltage690 - 690V
Overload release current setting100 - 125A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
Adjustment range short-term delayed short-circuit release0 - 0A
Adjustment range undelayed short-circuit release6 - 10A
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitFrame clamp
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalYes
Number of auxiliary contacts as normally closed contact0
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
With switched-off indicatorNo
With integrated under voltage releaseNo
Number of poles4
Type of control elementRocker lever
Position of connection for main current circuitFront side
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalNo
Degree of protection (IP)IP20
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMS1-4-A125 | Circuit-breaker, 4p, Icu=70kA(415V), In=125A, circuit.prot, thermomag, fixed.mount,

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

125A

Rated voltage

690 .. 690V

Overload release current setting

100 .. 125A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

Adjustment range short-term delayed short-circuit release

0 .. 0A

Adjustment range undelayed short-circuit release

6 .. 10A

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Frame clamp

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

With switched-off indicator

With integrated under voltage release

Number of poles

4

Type of control element

Rocker lever

Position of connection for main current circuit

Front side

Complete device with protection unit

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP20