Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
NZMS2-A100-SVE | Circuit-breaker, 3p, Icu=70kA(415V), In=100A, circuit.prot, thermomag, plug-in

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Overload release current setting
80 .. 100A
Adjustment range short-term delayed short-circuit release
0 .. 0A
Device construction
Built-in device plug-in technique
Adjustment range undelayed short-circuit release
600 .. 1000A
Type of electrical connection of main circuit
Screw connection
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Back side
Motor drive integrated
Motor drive optional
Type of control element
Rocker lever
Degree of protection (IP)
IP20
Complete device with protection unit
Rated permanent current Iu
100A
Number of poles
3
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA