Version as maintenance-/service switchNo
Version as emergency stop installationYes
Version as safety switchNo
Version as reversing switchNo
Rated operating voltage690 - 690V
Number of auxiliary contacts as normally closed contact0
Voltage release optionalNo
Suitable for distribution board installationNo
Suitable for front mounting centreNo
Device constructionComplete device in housing
Suitable for intermediate mountingNo
Suitable for front mounting 4-holeNo
Type of control elementShort thumb-grip
Rated permanent current at AC-23, 400 V80A
Switching power at 400 V55kW
Rated operation power at AC-3, 400 V30kW
Rated permanent current at AC-21, 400 V80A
Rated operation power at AC-23, 400 V30kW
Rated short-time withstand current lcw2kA
Conditioned rated short-circuit current Iq80kA
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
Type of electrical connection of main circuitScrew connection
With pre-assembled cablingNo
Colour control elementRed
Suitable for floor mountingYes
Degree of protection (NEMA)12
Degree of protection (IP), front sideIP65
Rated permanent current Iu80A
Max. rated operation voltage Ue AC690V