Details
- •Low-voltage industrial components
- •Motor protection circuit-breaker
- •1 KOM
- •EATON
Technical specifications
PKZM0-6,3-SPI16/AK | Motor starter with lockable rotary handle, screw+Push-in terminals, Ir=4-6.3A

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- EATON
Technical specifications
Overload release current setting
4 .. 6.3A
Adjustment range undelayed short-circuit release
98 .. 98A
With thermal protection
Rated operating voltage
690 .. 690V
Switch off technique
Thermomagnetic
Phase failure sensitive
Rated permanent current Iu
6.3A
Rated operation power at AC-3, 400 V
2.2kW
Rated operation power at AC-3, 230 V
1.1kW
Power loss
5.68W
Type of control element
Turn button
Type of electrical connection of main circuit
Screw-/spring clamp connection
Device construction
Built-in device fixed built-in technique
With integrated auxiliary switch
With integrated under voltage release
Number of poles
3
Degree of protection (IP)
IP20
Rated short-circuit breaking capacity lcu at 400 V, AC
150kA
Width
45mm
Height
93mm
Depth
77mm