Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Combined arrester for power supply systems
  • 1 KOM
  • EATON

Technical specifications

System configuration DCNo
System configuration ITNo
System configuration TNYes
System configuration TN-CNo
System configuration TN-C-SNo
Lightning impulse current (10/350 µs)50kA
System configuration TN-SNo
Max. continuous voltage DC0V
System configuration TTNo
Max. continuous voltage AC260V
Number of poles1
Specific energy (W/R)625kJ/Ohm
Construction size1 modular spacing
Max. overcurrent protection device, parallel connection (fuse)0A
Max. conductor cross section flexible (fine-strand)25mm²
Max. overcurrent protection device, series connection (fuse)0A
Mounting methodDIN rail (top hat rail) 35 mm
Test classType 1 + 2
Nominal voltage AC240V
Max. conductor cross section solid (solid, stranded)35mm²
Signalling at the deviceOptic
Nominal voltage DC0V
Voltage protection level L-N0kV
Voltage protection level1.4kV
System configuration otherYes
Voltage protection level (DC+ - DC-)0kV
Max. PV-voltage0V
Voltage protection level L-PE1.5kV
Voltage protection level N-PE1.4kV
Follow current extinguishing capability0kA
Voltage protection level (DC+/DC- - PE)0kV
Integrated backup fuseNo
Degree of protection (IP)IP20
Overcurrent protected voltage tappingNo
Energy-coordinated protection effect with regard to the terminal equipmentNo
Remote signallingNo
Voltage switching spark gap technologyYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

SPBT12-NPE50 | Surge arresters, class T1+T2 (b+c), N-pe, Iimp=50kA

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Combined arrester for power supply systems
  • 1 KOM
  • EATON

Technical specifications

System configuration DC

System configuration IT

System configuration TN

System configuration TN-C

System configuration TN-C-S

Lightning impulse current (10/350 µs)

50kA

System configuration TN-S

Max. continuous voltage DC

0V

System configuration TT

Max. continuous voltage AC

260V

Number of poles

1

Specific energy (W/R)

625kJ/Ohm

Construction size

1 modular spacing

Max. overcurrent protection device, parallel connection (fuse)

0A

Max. conductor cross section flexible (fine-strand)

25mm²

Max. overcurrent protection device, series connection (fuse)

0A

Mounting method

DIN rail (top hat rail) 35 mm

Test class

Type 1 + 2

Nominal voltage AC

240V

Max. conductor cross section solid (solid, stranded)

35mm²

Signalling at the device

Optic

Nominal voltage DC

0V

Voltage protection level L-N

0kV

Voltage protection level

1.4kV

System configuration other

Voltage protection level (DC+ - DC-)

0kV

Max. PV-voltage

0V

Voltage protection level L-PE

1.5kV

Voltage protection level N-PE

1.4kV

Follow current extinguishing capability

0kA

Voltage protection level (DC+/DC- - PE)

0kV

Integrated backup fuse

Degree of protection (IP)

IP20

Overcurrent protected voltage tapping

Energy-coordinated protection effect with regard to the terminal equipment

Remote signalling

Voltage switching spark gap technology

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.