Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Lightning current arrester for power supply systems
  • 1 KOM
  • PHOENIX

Technical specifications

System configuration DCNo
System configuration TN-CNo
System configuration otherNo
System configuration ITNo
System configuration TN-SYes
Lightning impulse current (10/350 µs)25kA
System configuration TN-C-SNo
Max. continuous voltage AC264V
System configuration TTNo
Follow current extinguishing capability50kA
Construction sizeOther
Voltage protection level L-N2.5kV
Voltage protection level N-PE1.5kV
Mounting methodDIN rail (top hat rail) 35 mm
Max. conductor cross section flexible (fine-strand)25mm²
System configuration TNNo
Max. conductor cross section solid (solid, stranded)35mm²
With remote signalling contactYes
Signalling at the deviceOptic
Category type 1Yes
Degree of protection (IP)IP20
Suitable for outdoor useNo
ExhaustingNo
Integrated backup fuseYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1461300 | FLT-MB-T1-264/25-1+1-UT-R

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Lightning current arrester for power supply systems
  • 1 KOM
  • PHOENIX

Technical specifications

System configuration DC

System configuration TN-C

System configuration other

System configuration IT

System configuration TN-S

Lightning impulse current (10/350 µs)

25kA

System configuration TN-C-S

Max. continuous voltage AC

264V

System configuration TT

Follow current extinguishing capability

50kA

Construction size

Other

Voltage protection level L-N

2.5kV

Voltage protection level N-PE

1.5kV

Mounting method

DIN rail (top hat rail) 35 mm

Max. conductor cross section flexible (fine-strand)

25mm²

System configuration TN

Max. conductor cross section solid (solid, stranded)

35mm²

With remote signalling contact

Signalling at the device

Optic

Category type 1

Degree of protection (IP)

IP20

Suitable for outdoor use

Exhausting

Integrated backup fuse

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.