System configuration DCNo
System configuration TN-CNo
System configuration otherNo
System configuration ITNo
System configuration TN-SYes
System configuration TN-C-SNo
Max. continuous voltage AC264V
System configuration TTNo
Follow current extinguishing capability50kA
Voltage protection level L-N2.5kV
Voltage protection level N-PE1.5kV
Max. conductor cross section flexible (fine-strand)25mm²
System configuration TNNo
Max. conductor cross section solid (solid, stranded)35mm²
With remote signalling contactYes
Signalling at the deviceOptic
Degree of protection (IP)IP20
Suitable for outdoor useNo
Integrated backup fuseYes
Mounting methodDIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs)25kA