System configuration DCNo
System configuration TNNo
System configuration TN-SYes
System configuration TN-C-SNo
System configuration ITNo
System configuration otherNo
Max. continuous voltage AC275V
System configuration TTNo
Voltage protection level1.6kV
Max. discharge surge current (8/20)40kA
Max. overcurrent protection device, series connection (fuse)80A
Max. overcurrent protection device, parallel connection (fuse)315A
Voltage protection level L-N1.35kV
Voltage protection level N-PE1.5kV
Short-circuit breaking capacity (Isccr)50kA
System configuration TN-CNo
Integrated backup fuseYes
Max. conductor cross section solid (solid, stranded)1.5mm²
Mounting methodDIN rail (top hat rail) 35 mm
Max. conductor cross section flexible (fine-strand)35mm²
Signalling at the deviceOptic
With remote signalling contactYes
Nominal discharge surge current (8/20)20kA