Technical specifications
System configuration IT
System configuration TN-C-S
Nominal discharge surge current (8/20)
20kA
System configuration TT
System configuration TN-C
Voltage protection level L-N
1.8kV
Max. continuous voltage AC
385V
Voltage protection level
2kV
Max. overcurrent protection device, parallel connection (fuse)
315A
Max. overcurrent protection device, series connection (fuse)
80A
Integrated backup fuse
Voltage protection level N-PE
1.5kV
Max. discharge surge current (8/20)
40kA
System configuration DC
Short-circuit breaking capacity (Isccr)
50kA
System configuration other
System configuration TN
System configuration TN-S
Leakage-current free
Max. conductor cross section solid (solid, stranded)
1.5mm²
Signalling at the device
Optic
With remote signalling contact
Max. conductor cross section flexible (fine-strand)
35mm²
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
Other
Category type 2