Details
- •Earthing, lightning and surge protection
- •Surge protection device for power supply systems
- •1 KOM
- •PHOENIX
Technical specifications
1466615 | VAL-SPP-T2-440-3+0-UT-R

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- PHOENIX
Technical specifications
System configuration IT
System configuration TN-C
System configuration other
Voltage protection level L-N
2.1kV
Max. discharge surge current (8/20)
40kA
Max. overcurrent protection device, parallel connection (fuse)
315A
Max. overcurrent protection device, series connection (fuse)
80A
System configuration TT
Leakage-current free
Nominal discharge surge current (8/20)
20kA
Short-circuit breaking capacity (Isccr)
50kA
System configuration TN
Integrated backup fuse
Mounting method
DIN rail (top hat rail) 35 mm
System configuration TN-S
Max. continuous voltage AC
440V
System configuration TN-C-S
System configuration DC
With remote signalling contact
Signalling at the device
Optic
Category type 2
Max. conductor cross section solid (solid, stranded)
1.5mm²
Max. conductor cross section flexible (fine-strand)
35mm²
Construction size
Other