System configuration TTNo
System configuration TN-CYes
System configuration TNNo
System configuration DCNo
System configuration ITNo
System configuration otherNo
System configuration TN-SNo
Max. continuous voltage AC440V
System configuration TN-C-SNo
Max. overcurrent protection device, parallel connection (fuse)250A
Short-circuit breaking capacity (Isccr)25kA
Mounting methodDIN rail (top hat rail) 35 mm
Max. discharge surge current (8/20)40kA
Max. overcurrent protection device, series connection (fuse)80A
Integrated backup fuseYes
Voltage protection level L-N2.5kV
With remote signalling contactYes
Max. conductor cross section solid (solid, stranded)1.5mm²
Max. conductor cross section flexible (fine-strand)35mm²
Signalling at the deviceOptic
Nominal discharge surge current (8/20)20kA