Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA124717R1 | E1.3C 630 Ekip Aware LI 3p F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
630A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range short-term delayed short-circuit release
- .. -A
Overload release current setting
252.0 .. 630A
Adjustment range undelayed short-circuit release
945.0 .. 9450A
Power loss
31W
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of poles
3
Complete device with protection unit
Motor drive integrated
Motor drive optional
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Type of control element
Push button