Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Rated permanent current Iu1000A
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release1500 - 15000A
Adjustment range short-term delayed short-circuit release600 - 10000A
Power loss78W
Overload release current setting400 - 1000A
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionNo
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Number of poles3
Motor drive optionalYes
Position of connection for main current circuitBack side
Degree of protection (IP)IP30
Motor drive integratedNo
Type of control elementPush button
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user