Technical specifications

Rated permanent current Iu2000A
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionNo
Type of electrical connection of main circuitBolt connection
Adjustment range short-term delayed short-circuit release1200 - 20000A
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release3000 - 30000A
Number of auxiliary contacts as normally closed contact0
Power loss212W
Number of auxiliary contacts as normally open contact0
Overload release current setting800 - 2000A
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
Position of connection for main current circuitBack side
Motor drive optionalYes
Type of control elementPush button
Motor drive integratedNo
Complete device with protection unitYes
Number of poles3
Degree of protection (IP)IP30