Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu4000A
Integrated earth fault protectionNo
Overload release current setting1600.0 - 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Power loss465W
Adjustment range undelayed short-circuit release6000.0 - 60000A
Adjustment range short-term delayed short-circuit release2400.0 - 40000A
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact0
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitBolt connection
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Type of control elementPush button
Number of poles3
Motor drive integratedNo
Complete device with protection unitYes
Position of connection for main current circuitBack side
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA124928R1 | E4.3H4000EkipAwareLSI3pFHR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Rated permanent current Iu

4000A

Integrated earth fault protection

Overload release current setting

1600.0 .. 4000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Power loss

465W

Adjustment range undelayed short-circuit release

6000.0 .. 60000A

Adjustment range short-term delayed short-circuit release

2400.0 .. 40000A

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally open contact

0

With integrated under voltage release

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Type of control element

Push button

Number of poles

3

Motor drive integrated

Complete device with protection unit

Position of connection for main current circuit

Back side

Motor drive optional

Degree of protection (IP)

IP30

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.