Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA124958R1 | E6.3V5000EkipAwareLSI3pFHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
5000A
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Power loss
483W
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2000.0 .. 5000A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of poles
3
Complete device with protection unit
Motor drive integrated
Position of connection for main current circuit
Back side
Type of control element
Push button
Motor drive optional
Degree of protection (IP)
IP30