Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA125010R1 | E1.3N800EkipAwareLSI4pFF
Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Overload release current setting
320.0 .. 800A
Power loss
50W
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
800A
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
With integrated under voltage release
Number of poles
4
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30