Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Power loss201W
Device constructionBuilt-in device fixed built-in technique
Overload release current setting640 - 1600A
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release960 - 16000A
Rated permanent current Iu1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Rated voltage690 - 690V
Adjustment range undelayed short-circuit release2400 - 24000A
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
With integrated under voltage releaseNo
With switched-off indicatorYes
Position of connection for main current circuitBack side
Type of control elementPush button
Motor drive integratedNo
Complete device with protection unitYes
Number of poles4
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user