Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA125124R1 | E2.3B2000EkipAwareLI4pFHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated voltage
690 .. 690V
Overload release current setting
800.0 .. 2000A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Adjustment range short-term delayed short-circuit release
- .. -A
Power loss
212W
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
With integrated under voltage release
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of poles
4
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional