  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Rated permanent current Iu2500A
Rated voltage690 - 690V
Adjustment range short-term delayed short-circuit release- - -A
Overload release current setting1000 - 2500A
Adjustment range undelayed short-circuit release3750 - 37500A
Power loss267W
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as change-over contact4
Integrated earth fault protectionNo
Type of electrical connection of main circuitBolt connection
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitBack side
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes
Number of poles4
Type of control elementPush button
Degree of protection (IP)IP30