Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Rated permanent current Iu2500A
Rated voltage690 - 690V
Adjustment range short-term delayed short-circuit release- - -A
Overload release current setting1000.0 - 2500A
Adjustment range undelayed short-circuit release3750.0 - 37500A
Power loss267W
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as change-over contact4
Integrated earth fault protectionNo
Type of electrical connection of main circuitBolt connection
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitBack side
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes
Number of poles4
Type of control elementPush button
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA125149R1 | E2.3S2500EkipAwareLI4pFHR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Rated permanent current Iu

2500A

Rated voltage

690 .. 690V

Adjustment range short-term delayed short-circuit release

- .. -A

Overload release current setting

1000.0 .. 2500A

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Power loss

267W

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as change-over contact

4

Integrated earth fault protection

Type of electrical connection of main circuit

Bolt connection

With integrated under voltage release

Number of auxiliary contacts as normally open contact

0

With switched-off indicator

Number of auxiliary contacts as normally closed contact

0

Position of connection for main current circuit

Back side

Complete device with protection unit

Motor drive integrated

Motor drive optional

Number of poles

4

Type of control element

Push button

Degree of protection (IP)

IP30