Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA125209R1 | E6.3H4000EkipAwareLI4pFHR
Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
- .. -A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
Overload release current setting
1600.0 .. 4000A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Power loss
309W
Number of poles
4
Complete device with protection unit
Type of control element
Push button
Motor drive integrated
Motor drive optional
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30