Aleta.hr
Announcement

Registration is currently available to business customers only (B2B).

Details

  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release6000 - 60000A
Integrated earth fault protectionNo
Number of auxiliary contacts as normally closed contact0
Device constructionBuilt-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release- - -A
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
Overload release current setting1600 - 4000A
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
Rated permanent current Iu4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Power loss309W
Number of poles4
Complete device with protection unitYes
Type of control elementPush button
Motor drive integratedNo
Motor drive optionalYes
Position of connection for main current circuitBack side
Degree of protection (IP)IP30