Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage690 - 690V
Adjustment range short-term delayed short-circuit release- - -A
Overload release current setting2520.0 - 6300A
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA
Rated permanent current Iu6300A
Adjustment range undelayed short-circuit release9450.0 - 94500A
Power loss767W
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
Position of connection for main current circuitBack side
Number of poles4
Type of control elementPush button
Motor drive integratedNo
Complete device with protection unitYes
Degree of protection (IP)IP30
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA125294R1 | E6.3X/f6300EkipAwareLI4pFHR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Adjustment range short-term delayed short-circuit release

- .. -A

Overload release current setting

2520.0 .. 6300A

Device construction

Built-in device fixed built-in technique

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

-kA

Rated permanent current Iu

6300A

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Power loss

767W

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally open contact

0

With switched-off indicator

Number of auxiliary contacts as normally closed contact

0

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as change-over contact

4

With integrated under voltage release

Position of connection for main current circuit

Back side

Number of poles

4

Type of control element

Push button

Motor drive integrated

Complete device with protection unit

Degree of protection (IP)

IP30

Motor drive optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.