Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu1000A
Rated voltage690 - 690V
Overload release current setting400 - 1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release1500 - 15000A
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release600 - 10000A
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as change-over contact4
Power loss113W
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With switched-off indicatorYes
With integrated under voltage releaseNo
Position of connection for main current circuitConnection at separate chassis part
Number of poles3
Complete device with protection unitYes
Motor drive optionalYes
Motor drive integratedNo
Type of control elementPush button
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user