Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Power loss176W
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release1875.0 - 18750A
Number of auxiliary contacts as change-over contact4
Rated permanent current Iu1250A
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally open contact0
Overload release current setting500.0 - 1250A
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Rated voltage690 - 690V
Adjustment range short-term delayed short-circuit release- - -A
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of electrical connection of main circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
Number of poles3
Type of control elementPush button
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA125406R1 | E2.3N1250EkipAwareLI3pWMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

Power loss

176W

Integrated earth fault protection

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Number of auxiliary contacts as change-over contact

4

Rated permanent current Iu

1250A

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally open contact

0

Overload release current setting

500.0 .. 1250A

With switched-off indicator

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Rated voltage

690 .. 690V

Adjustment range short-term delayed short-circuit release

- .. -A

Device construction

Built-in device slide-in technique (withdrawable)

Type of electrical connection of main circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

Type of control element

Push button

Position of connection for main current circuit

Connection at separate chassis part

Complete device with protection unit

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP30

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.