Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA125422R1 | E2.3B1600EkipAwareLSI3pWMP
Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Power loss
288W
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
With integrated under voltage release
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Degree of protection (IP)
IP30
Motor drive optional
Motor drive integrated
Number of poles
3
Complete device with protection unit