Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu2000A
Adjustment range short-term delayed short-circuit release- - -A
Power loss450W
Adjustment range undelayed short-circuit release3000 - 30000A
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally closed contact0
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally open contact0
Overload release current setting800 - 2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Number of poles3
Complete device with protection unitYes
Position of connection for main current circuitConnection at separate chassis part
Type of control elementPush button
Degree of protection (IP)IP30
Motor drive optionalYes
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user