Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting2000.0 - 5000A
Rated voltage690 - 690V
Rated permanent current Iu5000A
Integrated earth fault protectionNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA
Adjustment range short-term delayed short-circuit release3000.0 - 50000A
Suitable for DIN rail (top hat rail) mountingNo
With integrated under voltage releaseNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Power loss850W
Adjustment range undelayed short-circuit release7500.0 - 75000A
With switched-off indicatorYes
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally open contact0
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Number of poles3
Motor drive integratedNo
Complete device with protection unitYes
Position of connection for main current circuitConnection at separate chassis part
Motor drive optionalYes
Type of control elementPush button
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA125552R1 | E6.3X5000EkipAwareLSI3pWMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

2000.0 .. 5000A

Rated voltage

690 .. 690V

Rated permanent current Iu

5000A

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

-kA

Adjustment range short-term delayed short-circuit release

3000.0 .. 50000A

Suitable for DIN rail (top hat rail) mounting

With integrated under voltage release

Device construction

Built-in device slide-in technique (withdrawable)

Power loss

850W

Adjustment range undelayed short-circuit release

7500.0 .. 75000A

With switched-off indicator

Type of electrical connection of main circuit

Connection at separate chassis part

Number of auxiliary contacts as normally open contact

0

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Number of poles

3

Motor drive integrated

Complete device with protection unit

Position of connection for main current circuit

Connection at separate chassis part

Motor drive optional

Type of control element

Push button

Degree of protection (IP)

IP30

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.