Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu800A
Adjustment range short-term delayed short-circuit release- - -A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Adjustment range undelayed short-circuit release1200.0 - 12000A
Type of electrical connection of main circuitConnection at separate chassis part
Power loss100W
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Overload release current setting320.0 - 800A
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
With switched-off indicatorYes
Number of auxiliary contacts as normally open contact0
Type of control elementPush button
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Complete device with protection unitYes
Number of poles4
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA125593R1 | E1.3C800EkipAwareLI4pWMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Rated permanent current Iu

800A

Adjustment range short-term delayed short-circuit release

- .. -A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Type of electrical connection of main circuit

Connection at separate chassis part

Power loss

100W

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Overload release current setting

320.0 .. 800A

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as change-over contact

4

With integrated under voltage release

With switched-off indicator

Number of auxiliary contacts as normally open contact

0

Type of control element

Push button

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

Complete device with protection unit

Number of poles

4

Motor drive optional

Degree of protection (IP)

IP30