Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Device constructionBuilt-in device slide-in technique (withdrawable)
Power loss400W
Overload release current setting640 - 1600A
Integrated earth fault protectionNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Adjustment range undelayed short-circuit release2400 - 24000A
Suitable for DIN rail (top hat rail) mountingNo
Rated permanent current Iu1600A
Rated voltage690 - 690V
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release960 - 16000A
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Number of poles4
Complete device with protection unitYes
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Motor drive optionalYes
Motor drive integratedNo
Type of control elementPush button
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user