Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA125673R1 | E2.3H1000EkipAwareLI4pWMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1000A
Overload release current setting
400.0 .. 1000A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Power loss
113W
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
- .. -A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of poles
4
Complete device with protection unit
Motor drive optional
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Motor drive integrated