Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Power loss288W
Adjustment range undelayed short-circuit release2400.0 - 24000A
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu1600A
Adjustment range short-term delayed short-circuit release- - -A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Overload release current setting640.0 - 1600A
Rated voltage690 - 690V
Type of electrical connection of main circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
With integrated under voltage releaseNo
Number of poles4
Complete device with protection unitYes
Position of connection for main current circuitConnection at separate chassis part
Type of control elementPush button
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA125703R1 | E2.3S1600EkipAwareLI4pWMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Power loss

288W

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

1600A

Adjustment range short-term delayed short-circuit release

- .. -A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Overload release current setting

640.0 .. 1600A

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

With integrated under voltage release

Number of poles

4

Complete device with protection unit

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP30