  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Overload release current setting1280 - 3200A
Adjustment range short-term delayed short-circuit release- - -A
Power loss743W
Adjustment range undelayed short-circuit release4800 - 48000A
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitConnection at separate chassis part
Type of control elementPush button
Number of poles4
Degree of protection (IP)IP30
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes