Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA125778R1 | E4.3N4000EkipAwareLI4pWMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
1600.0 .. 4000A
Adjustment range short-term delayed short-circuit release
- .. -A
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Type of electrical connection of main circuit
Connection at separate chassis part
Power loss
900W
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Type of control element
Push button
Motor drive integrated
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP30