Technical specifications

Rated permanent current Iu6300A
Adjustment range undelayed short-circuit release9450 - 94500A
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA
Number of auxiliary contacts as normally closed contact0
Overload release current setting2520 - 6300A
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitConnection at separate chassis part
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release- - -A
Device constructionBuilt-in device slide-in technique (withdrawable)
With switched-off indicatorYes
Power loss1550W
Suitable for DIN rail (top hat rail) mountingNo
With integrated under voltage releaseNo
Type of control elementPush button
Number of poles4
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Motor drive optionalYes
Complete device with protection unitYes
Degree of protection (IP)IP30