Aleta.hr
Announcement

Registration is currently available to business customers only (B2B).

Details

  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Adjustment range undelayed short-circuit release6000 - 60000A
Type of electrical connection of main circuitConnection at separate chassis part
Power loss544W
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Number of auxiliary contacts as change-over contact4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Overload release current setting1600 - 4000A
Adjustment range short-term delayed short-circuit release2400 - 40000A
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu4000A
With integrated under voltage releaseNo
Number of poles4
Type of control elementPush button
Complete device with protection unitYes
Position of connection for main current circuitConnection at separate chassis part
Motor drive optionalYes
Motor drive integratedNo
Degree of protection (IP)IP30