Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Integrated earth fault protectionYes
Rated voltage690 - 690V
Rated permanent current Iu1000A
Adjustment range short-term delayed short-circuit release600 - 10000A
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
Adjustment range undelayed short-circuit release1500 - 15000A
With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Power loss78W
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as change-over contact4
Overload release current setting400 - 1000A
Position of connection for main current circuitBack side
Number of poles3
Complete device with protection unitYes
Motor drive optionalYes
Motor drive integratedNo
Type of control elementPush button
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user