Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu1000A
Adjustment range short-term delayed short-circuit release600 - 10000A
Adjustment range undelayed short-circuit release1500 - 15000A
Overload release current setting400 - 1000A
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Power loss53W
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Number of poles3
Type of control elementPush button
Complete device with protection unitYes
Degree of protection (IP)IP30
Motor drive optionalYes
Position of connection for main current circuitBack side
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user