Technical specifications

Rated permanent current Iu1000A
Rated voltage690 - 690V
Overload release current setting400.0 - 1000A
Adjustment range short-term delayed short-circuit release600.0 - 10000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Power loss156W
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release1500.0 - 15000A
Integrated earth fault protectionYes
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Type of control elementPush button
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30
Number of poles3
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA128929R1 | E1.3N1000EkipAwareLSIG3pWMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1000A

Rated voltage

690 .. 690V

Overload release current setting

400.0 .. 1000A

Adjustment range short-term delayed short-circuit release

600.0 .. 10000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

Power loss

156W

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

1500.0 .. 15000A

Integrated earth fault protection

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

With integrated under voltage release

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

Position of connection for main current circuit

Connection at separate chassis part

Complete device with protection unit

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP30

Number of poles

3