Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu3200A
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release1920 - 32000A
With integrated under voltage releaseNo
Integrated earth fault protectionYes
Power loss743W
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of electrical connection of main circuitConnection at separate chassis part
Overload release current setting1280 - 3200A
Adjustment range undelayed short-circuit release4800 - 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Number of poles3
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Type of control elementPush button
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30