Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu3200A
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release1920.0 - 32000A
With integrated under voltage releaseNo
Integrated earth fault protectionYes
Power loss743W
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of electrical connection of main circuitConnection at separate chassis part
Overload release current setting1280.0 - 3200A
Adjustment range undelayed short-circuit release4800.0 - 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Number of poles3
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Type of control elementPush button
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA128960R1 | E4.3H3200EkipAwareLSIG3pWMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Rated permanent current Iu

3200A

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

With integrated under voltage release

Integrated earth fault protection

Power loss

743W

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

With switched-off indicator

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device slide-in technique (withdrawable)

Type of electrical connection of main circuit

Connection at separate chassis part

Overload release current setting

1280.0 .. 3200A

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Number of poles

3

Position of connection for main current circuit

Connection at separate chassis part

Complete device with protection unit

Type of control element

Push button

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP30

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.