Aleta.hr
Announcement

Registration is currently available to business customers only (B2B).

Details

  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Adjustment range short-term delayed short-circuit release480 - 8000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Adjustment range undelayed short-circuit release1200 - 12000A
Rated permanent current Iu800A
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitConnection at separate chassis part
With integrated under voltage releaseNo
Power loss100W
Rated voltage690 - 690V
Overload release current setting320 - 800A
With switched-off indicatorYes
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Integrated earth fault protectionYes
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Motor drive integratedNo
Number of poles4
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Type of control elementPush button
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as