Details

  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Adjustment range short-term delayed short-circuit release600 - 10000A
Rated permanent current Iu1000A
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated voltage690 - 690V
Power loss156W
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as change-over contact4
Integrated earth fault protectionYes
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
With switched-off indicatorYes
Adjustment range undelayed short-circuit release1500 - 15000A
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Overload release current setting400 - 1000A
Complete device with protection unitYes
Type of control elementPush button
Position of connection for main current circuitConnection at separate chassis part
Motor drive optionalYes
Motor drive integratedNo
Number of poles4
Degree of protection (IP)IP30