  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Overload release current setting400 - 1000A
Adjustment range undelayed short-circuit release1500 - 15000A
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu1000A
Power loss113W
Adjustment range short-term delayed short-circuit release600 - 10000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
Integrated earth fault protectionYes
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Type of control elementPush button
Number of poles4
Motor drive integratedNo
Degree of protection (IP)IP30
Motor drive optionalYes