Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu3200A
Rated voltage690 - 690V
Overload release current setting1280.0 - 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Adjustment range short-term delayed short-circuit release1920.0 - 32000A
Adjustment range undelayed short-circuit release4800.0 - 48000A
Power loss743W
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
With integrated under voltage releaseNo
Position of connection for main current circuitConnection at separate chassis part
Number of poles4
Type of control elementPush button
Degree of protection (IP)IP30
Motor drive integratedNo
Complete device with protection unitYes
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA129014R1 | E4.3S3200EkipAwareLSIG4pWMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

3200A

Rated voltage

690 .. 690V

Overload release current setting

1280.0 .. 3200A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Power loss

743W

Device construction

Built-in device slide-in technique (withdrawable)

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Connection at separate chassis part

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

With integrated under voltage release

Position of connection for main current circuit

Connection at separate chassis part

Number of poles

4

Type of control element

Push button

Degree of protection (IP)

IP30

Motor drive integrated

Complete device with protection unit

Motor drive optional