Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA129029R1 | E6.3X6300EkipAwareLSIG4pWMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Overload release current setting
2520.0 .. 6300A
Rated permanent current Iu
6300A
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
Power loss
1550W
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30