Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

System configuration DCNo
System configuration ITYes
System configuration TN-CYes
System configuration TNYes
System configuration otherNo
System configuration TN-C-SYes
System configuration TN-SYes
System configuration TTYes
Nominal discharge surge current (8/20)20kA
Number of conductors (without earthing)1
Max. discharge surge current (8/20)20kA
Max. continuous voltage AC440V
Nominal voltage DC-V
Nominal voltage AC230V
Max. continuous voltage DC-V
Max. PV-voltage-V
Voltage protection level1.4kV
Voltage protection level N-PE1.4kV
Voltage protection level L-N1.4kV
Max. overcurrent protection device, parallel connection (fuse)125A
Mounting methodOther
Integrated short-circuit protectionNo
Leakage-current freeNo
Construction size2 modular spacing
Integrated backup fuseNo
Category type 2Yes
Signalling at the deviceOptic
Max. overcurrent protection device, series connection (fuse)125A
Max. conductor cross section flexible (fine-strand)16mm²
With remote signalling contactNo
Degree of protection (IP)IP20
Short-circuit breaking capacity (Isccr)100kA
Integrated short-circuit protection selective to fuse gG-A
Max. conductor cross section solid (solid, stranded)25mm²
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CTB803876R0400 | OVR T2 40-440 C QS

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

System configuration DC

System configuration IT

System configuration TN-C

System configuration TN

System configuration other

System configuration TN-C-S

System configuration TN-S

System configuration TT

Nominal discharge surge current (8/20)

20kA

Number of conductors (without earthing)

1

Max. discharge surge current (8/20)

20kA

Max. continuous voltage AC

440V

Nominal voltage DC

-V

Nominal voltage AC

230V

Max. continuous voltage DC

-V

Max. PV-voltage

-V

Voltage protection level

1.4kV

Voltage protection level N-PE

1.4kV

Voltage protection level L-N

1.4kV

Max. overcurrent protection device, parallel connection (fuse)

125A

Mounting method

Other

Integrated short-circuit protection

Leakage-current free

Construction size

2 modular spacing

Integrated backup fuse

Category type 2

Signalling at the device

Optic

Max. overcurrent protection device, series connection (fuse)

125A

Max. conductor cross section flexible (fine-strand)

16mm²

With remote signalling contact

Degree of protection (IP)

IP20

Short-circuit breaking capacity (Isccr)

100kA

Integrated short-circuit protection selective to fuse gG

-A

Max. conductor cross section solid (solid, stranded)

25mm²

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.